Power Factor Correction
PFC Controller

1.Product Features


1. Real-time display of power factor φ, voltage, current, active power, reactive power, voltage total harmonic distortion rate, current total harmonic distortion rate, frequency, capacitance output display and switching status and various protection overrun alarms and other information.

2. Capacitor input delay and removal delay can be set separately, with high compensation efficiency, input and removal thresholds can be preset and high compensation accuracy.

3. It has the functions of harmonic voltage and current measurement and protection, and power failure protection; it has two working modes of manual compensation and automatic compensation; it has standard field bus communication interface which is convenient for connecting to the intelligent switch cabinet system.

4. Adhering to the people-oriented design concept, modular assembly, full digital design, the human-machine interface adopts a large-screen English LCD display.

5. Signal AC sampling, strong anti-interference ability, avoid misoperation, high work reliability; can accurately judge reactive power and power factor, and avoid oscillation switching phenomenon.

2.Technical Parameter



Environmental condition

Height above sea level

2500m

Temperature

-20°C~60°C

No conductive dust, no corrosive gas,no explosive and flammable medium around the controller. The installation site should be no violent vibration and erosion of snow and rain.

Input/output

signal

Sampling voltage

Phase splitting compensationL1/L2/L3 phase voltage

Total CompensationL1/L3 Phase

Sample current

Phase splitting compensationthe each phase current of L1/L2/L3 is 0~5A

Total compensationL2 is 0~5A

Control output

Relay5A/250V

Thyristor switch12V/30mA

Display Function

LCD monitor data refresh cycle1S

Measurement accuracy

Voltage

±0.5%

Current

±0.5%

Power factor

±1.0%

Active factor

±1.0%

Reactive factor

±1.0%

Frequency

±0.1Hz

ID setting

ID number

001~255

Communication rate

4800~38400bps

Measurement data

Voltage

100V~290V

Current

0~6000A

Sensitivity

50mA(Secondary)

Power factor

Lag 0.200~ahead 0.200

Power supply

220V±20%

Testing Frequency

47~53Hz

Active power

0~6553KW

Reactive power

0~6553Kvar

THD-V

0~100%

THD-I

0~100%

Communication interface data

Interface

RS-485

Protocol

MODBUS communication protocol

Setting data

Current transformer ratio

Rate value1~1200

Delay time

Contactor5 S~100 S Thyristor switch 0.1S~30S

Target power factor

Lag 0.9~ Ahead 1.0

Over voltage

230V~290V or close

Under voltage

180V~200V or close

Off limit

0.5-1.2

Harmonic voltage protection

1.0%~50% or close

Harmonic current protection

180V~200V or close

Phase splitting compensation capacitor branches

0~7

Three-splitting compensation capacitor branches

0~21

Capacitor branches

Three times phase splitting branches + three branches21

Capacitor preset

0~999Kvar/Branch







PFC Controller